Pass-through boxes (pass boxes) enable the safe, contamination-free transfer of materials between a cleanroom and adjacent areas. Equipped with interlocking doors and High-Efficiency Particulate Air (HEPA) filters, they prevent air contamination and enhance workflow efficiency.
This stainless steel, interlocking cleanroom pass-through box is designed for GMP-compliant cleanroom operations. It is available in three configurations: standard sterile pass-through boxes, laminar-flow sterile pass-through boxes, and air-shower pass-through boxes for cleanroom environments. The units meet ISO Class 5 cleanliness standards and the latest cGMP requirements, providing a reliable sterile transfer solution for facilities with stringent cleanliness standards.


Key Features
High-Quality Materials and Superior Airtightness
The main body and interior walls of the cleanroom pass-through hatch are constructed from thickened SUS304 stainless steel. The interior features a coved (radiused) design with no dead corners, facilitating easy daily cleaning and disinfection. Equipped with an integrated, adhesive-bonded foamed gasket, the unit offers excellent airtightness, effectively preventing external dust and microorganisms from entering the cleanroom environment.
01
Intelligent Interlocking and Multi-Stage Sterilization
Equipped with an LCJ-brand electronic interlocking system, the unit ensures electrical interlocks between the two doors, preventing them from being opened simultaneously and eliminating the risk of cross-contamination between different zones. It also features an integrated Philips UV germicidal lamp-with a service life of up to 8,000 hours-to sterilize the surfaces of items being transferred.
02
GMP Compliance
The aseptic laminar-flow pass box is equipped with a high-efficiency HEPA filter, offering a 99.99% filtration efficiency for 0.3μm particles. It includes built-in PAO aerosol injection ports and DOP test ports for verifying filter integrity. The unit achieves a cleanliness level of ISO Class 5 (surpassing the Federal Standard 209E Class 100 requirement).
03
Automated Design
The air-shower pass box utilizes photoelectric sensors to automatically trigger the air-shower cycle; the duration of the air-shower is fully customizable, with an outlet air velocity of ≥25 m/s. The laminar-flow model features an LCD touchscreen and a Dwyer (USA) differential pressure gauge. Users can configure the duration of laminar-flow operation and UV sterilization, and the system includes an automated reminder for HEPA filter replacement.
04
Technical Specifications of the Sterile Laminar Flow Pass Box
|
Configuration |
Specifications |
Optional Options |
|
Overall size (W×D×H) |
860×680×1250mm (external) |
1060×880×1450mm (external) |
|
Inner size (W×D×H) |
600×600×600mm |
800×800×800mm |
|
Main material |
SUS304 stainless steel |
External SPCC sprayed steel plate + inner SUS304 |
|
Interlock type |
LCJ electronic interlock |
/ |
|
Glass window |
Double-layer hollow black edge paint, 5mm tempered glass |
502×502×5mm / 650×650×5mm |
|
Germicidal lamp power |
8W/18W |
8-16W (customizable) |
|
Cleanliness standard |
ISO 5 (better than 209E class100) |
/ |
|
Wind speed |
0.45m/s ±20% |
/ |
|
Filtering system |
Flume HEPA (99.99%@0.3μm) |
520×520×93mm / 650×650×93mm |
|
Differential pressure gauge |
Dwyer 0-500Pa |
/ |
|
Inspection port |
SUS PAO dust outlet + DOP detection port |
/ |
|
Power supply |
AC220V 140W |
/ |
|
Handle type |
Snap-on stainless steel handle |
Customizable stainless steel handle |
HVAC Technology (Suzhou) Co., Ltd. offers customized solutions for stainless steel interlocked cleanroom pass-through boxes.
Customization of Dimensions and Materials
Specifications can be tailored based on the thickness of the cleanroom wall and the dimensions of the items to be transferred. A variety of material options are available-ranging from full SUS304 stainless steel to a hybrid configuration (powder-coated SPCC steel for the exterior and SUS304 stainless steel for the interior)-allowing clients to manage project costs while strictly meeting cleanliness requirements.
Customization of Features and Accessories
UV germicidal lamp wattage (8–16W) can be specified, and clients may select from various door handle styles and observation window sizes. For aseptic laminar-flow pass-through boxes, specialized configurations such as hinge-less designs and concealed UV germicidal lamps are available.
Customization of Design and Performance
For air-shower pass-through boxes, parameters such as airflow velocity and the duration of the sensor-activated air shower can be customized. For laminar-flow models, the filtration system can be optimized, and intelligent fault-alarm modules can be integrated. This multi-dimensional, personalized customization ensures that the equipment aligns with the unique operational requirements of diverse cleanroom projects.
FAQ
Q: Can electronic interlocks on pass-through boxes be replaced by mechanical interlocks?
A: Mechanical interlocks are acceptable for standard rooms with lower cleanliness requirements. For GMP-compliant sterile production areas, electronic interlocks are preferred; they offer higher reliability and are better suited for continuous production processes.
Q: What is the purpose of a DOP/PAO test port?
A: It is used for on-site integrity testing (leak testing) of HEPA filters and is a mandatory test interface for GMP compliance inspections.