A low-dew-point desiccant dehumidifier utilizes moisture-absorbing materials-such as silica gel or molecular sieves-to physically adsorb water vapor from the air, while employing a heating-based regeneration process to ensure continuous dehumidification. Capable of operating reliably in low-temperature and low-humidity environments, these units can achieve dew points as low as -70°C or below. They are widely used in industrial settings with stringent humidity requirements, including lithium-battery manufacturing, pharmaceuticals, and food processing.

Key Features
Core Components: The dehumidifiers from HVAC Technology utilize silica gel rotors manufactured by the Swedish company PROFLUTE. These enable the system to consistently achieve ultra-low dew points-down to -70°C-and ensure reliable, continuous operation even in low-temperature environments.
Ease of Operation: Equipped with an automated PLC-based control system, the unit maintains stable performance. A touchscreen human-machine interface (HMI) allows for intuitive and convenient operation.
Optimized Design: The unit features a modular design, facilitating on-site transport, assembly/disassembly, and long-term maintenance.
Superior Performance: The unit's frame is constructed from thermally broken aluminum alloy profiles, combined with polyurethane foam-insulated panels. This design provides excellent thermal insulation, effectively minimizing cooling loss.
Specifications
|
Parametersmodel |
ADL-E2000 |
ADL-E3500 |
ADL-E6000 |
ADL-E9000 |
ADL-E12000 |
ADL-E16000 |
ADL-E21000 |
ADL-E26000 |
|
Airflow range (m³/h) |
1500-2000 |
3000-3500 |
5500-6000 |
8500-9000 |
11000-12000 |
15000-16000 |
20000-21000 |
25000-26000 |
|
Processing airflow (m³/h) |
2000 |
3500 |
6000 |
9000 |
12000 |
16000 |
21000 |
26000 |
|
Regeneration airflow (m³/h) |
350 |
600 |
1000 |
1500 |
2000 |
2650 |
3500 |
4350 |
|
Minimum outlet dew point (°Cd) |
-70 |
-70 |
-70 |
-70 |
-70 |
-70 |
-70 |
-70 |
|
Regeneration energy consumption (kW) |
14.5 |
25 |
41 |
61.5 |
82 |
111 |
143.5 |
182 |
|
Processing fan power (kW) |
2.2 |
2.6 |
5.2 |
9.5 |
13 |
18.5 |
26 |
30 |
|
Regeneration fan power (kW) |
0.55 |
0.75 |
1.1 |
1.5 |
2.2 |
3 |
4 |
5.5 |
|
Drive motor power (kW) |
0.12 |
0.12 |
0.12 |
0.12 |
0.18 |
0.18 |
0.24 |
0.24 |
|
Total power (kW) |
17.37 |
28.47 |
47.42 |
72.62 |
97.38 |
132.68 |
173.74 |
217.74 |
Available Unit Types
Standard Single-Stage Desiccant Dehumidification Units
Designed for general low-humidity and cleanroom applications; utilize silica gel desiccant wheels; offer an excellent balance of performance and cost.
01
Two-Stage Ultra-Low Dew Point Units
Engineered for high-specification environments (such as lithium-ion battery manufacturing); utilize molecular sieve desiccant wheels to achieve deep dehumidification.
02
Modular Purification and Dehumidification Air Handling Units
Integrated systems combining pre-cooling, desiccant dehumidification, post-cooling, and filtration; the most common choice for cleanroom environments.
03
Compact Cabinet-Style Desiccant Dehumidifiers
Suitable for low-airflow laboratory settings or retrofit projects in smaller, enclosed spaces.
04
FAQ
Q: Does Hanweisi only manufacture dehumidifiers, or do you also provide complete purification engineering solutions?
A: HVAC Technology acts as both an equipment supplier and an EPC (Engineering, Procurement, and Construction) integrator for industrial environments. We can supply individual desiccant dehumidification units or undertake complete, turnkey projects for constant-temperature and constant-humidity purification systems in cleanrooms-covering everything from design and manufacturing to installation, commissioning, and after-sales service.
Q: For cleanroom applications, should I choose a silica gel or a molecular sieve desiccant rotor?
A: For standard cleanrooms requiring a relative humidity (RH) of 20%–40%, a silica gel rotor is recommended, as it operates at a lower regeneration temperature and offers superior energy efficiency. For environments such as lithium-battery electrolyte-filling rooms, which require a dew point below -40°C, a molecular sieve rotor should be used.
Q: How can the energy consumption of the units be optimized?
A: Energy consumption can be optimized by adding a regeneration heat recovery section, which captures heat from the regeneration exhaust air to preheat the incoming regeneration air, significantly reducing the energy required for regeneration heating. Additionally, prioritizing steam or hot water as a heat source-rather than relying solely on electric heating-can lower long-term operational costs.
Hot Tags: low dew point dehumidifier, China low dew point dehumidifier manufacturers, suppliers, factory, Rotary Dehumidifier